Skip to content
English - United Kingdom
  • There are no suggestions because the search field is empty.

Electric Combi Boiler - No heating!

How to fault-find and fix an Electric Combi Boiler when the heating side is not 'firing'.

Use this guide when the room thermostat is calling for heat but the boiler does not respond, or the call-for-heat signal is intermittent.


1. Confirm Boiler is in Winter Mode

Before any fault-finding, confirm the boiler is set to heating mode.

  • Check the boiler display:

    • Snowflake symbol = Winter mode (heating + hot water enabled)

    • Sun symbol = Summer mode (hot water only, no heating)

If the boiler is in Summer mode:

  • Press the Menu button until the snowflake symbol appears

  • Re-check whether the boiler responds to heating demand

If already in Winter mode, continue.


2. Safety and Initial Setup

  • Confirm the system is safe to work on

  • Ensure electrical isolation is available before opening any controls

  • Record starting conditions:

    • Time on site

    • Ambient temperature

    • System pressure

    • Thermostat setpoint and room temperature

    • Boiler flow temperature setpoint


3. Verify Heating System Flow (Rule Out Blockages)

Before investigating controls or wiring, confirm the heating system can circulate properly.

Check the following:

  • All boiler flow and return isolation valves are open

  • Any zone valves are open and operating

  • All radiator TRVs are fully open (set to maximum)

  • Lockshield valves are not closed

  • If using underfloor heating:

    • All actuator heads are open

    • Manifold valves are open and not stuck closed

  • Pump runs when heating demand is present

  • Flow pipe warms up and return responds

If circulation is restricted, correct the flow issue first.

If flow is confirmed OK, continue.


4. Check Call-for-Heat Signal at Each Stage

Confirm the call-for-heat is present through the full control chain.

  1. Room thermostat

  • Raise setpoint above room temperature

  • Confirm thermostat shows demand for heat

  1. Receiver/control box

  • Confirm thermostat and receiver are connected/paired

  • Confirm receiver indicator shows call-for-heat

  1. Boiler

  • Confirm boiler display shows call-for-heat input (if applicable)

If thermostat and receiver show demand but boiler does not, the signal is being lost between receiver and boiler.


5. Check Wiring Inside the Receiver Box (Most Common Fix)

Most faults of this type are caused by poor terminations inside the receiver.

Steps:

  • Isolate power

  • Open the receiver/control box

  • Inspect call-for-heat terminals and wiring

  • Check for:

    • Loose screws

    • Poorly stripped conductors

    • Stray copper strands

    • Damaged or stretched cable

  • Remake and tighten all call-for-heat signal connections

  • Restore power and retest boiler response

If fault is resolved, close out.

If not resolved, continue.


6. Prove Boiler Operation with Temporary Bridge Test

If receiver wiring does not resolve the issue, prove whether the boiler can fire correctly.

Steps:

  • Isolate power

  • Locate boiler call-for-heat input terminals

  • Temporarily bridge the call-for-heat input (diagnostic use only)

  • Restore power and observe operation

Results:

  • Boiler fires and cycles normally:

    • Boiler is functional

    • Fault remains in controls, wiring, or receiver output

  • Boiler does not fire:

    • Boiler-side fault likely (PCB, sensors, internal wiring, lockout)

Remove bridge after test and reinstate correct wiring.


7. Continuity Test the Call-for-Heat Signal Wire

If the fault is intermittent, test the signal cable between receiver and boiler.

Steps:

  • Identify call-for-heat conductors

  • Test continuity end-to-end

  • Leave tester connected during operation to detect dropouts

Interpretation:

  • Continuity stable:

    • Wiring likely OK

    • Suspect receiver switching output or boiler input stage

  • Continuity drops in and out:

    • Cable break, loose termination, or faulty receiver terminal


8. Fix Terminations and Connections Properly

If wiring faults are suspected:

  • Strip conductors cleanly

  • Ensure no insulation is trapped under terminals

  • Ensure no stray strands

  • Use secure connectors (e.g., Wago) if required

  • Add strain relief so cables cannot pull loose

Retest for at least one full heating cycle.


9. Swap in a Known-Good Receiver/Control Box

If receiver output remains unreliable:

  • Replace with a known working receiver/control box

  • Pair with thermostat

  • Confirm call-for-heat appears at:

    • Thermostat

    • Receiver

    • Boiler

If fault disappears, original receiver/control box is faulty.


10. Verify Heating Operation and Cycling

Once repaired, confirm normal heating performance:

  • Boiler fires reliably

  • Pump runs correctly

  • Radiators warm up

  • Boiler reaches flow setpoint and modulates

  • Boiler shuts down at setpoint and refires after differential drop


11. Domestic Hot Water Changeover Test (Combi Systems)

If boiler provides DHW:

  • Run hot water and confirm DHW mode activates

  • Stop hot water and confirm boiler returns to heating demand

  • Heating should refire once temperature drops below threshold


12. Final Stability Check and Close-Out

  • Leave system running on normal controls

  • Observe at least one complete heating cycle

  • If possible, return later to confirm continued stable operation

  • Document any outstanding issues for supplier escalation


Common Fault Causes Identified by This Process

  • Boiler left in Summer mode (sun symbol)

  • Closed valves or restricted circulation

  • Loose termination inside receiver box (most common electrical cause)

  • Intermittent call-for-heat signal cable fault

  • Faulty receiver/control output

  • Boiler PCB or input recognition fault